|
Article V. Fire Alarm Systems
Sec. 30-117 Definitions
As used in
this article, the following terms shall have the meanings ascribed to them
in this section.
Approval shall mean with the approval and consent of the fire chief
of the city or his/ her designee.
Required systems shall mean fire alarm systems that are required by
this article or of other state, local or federal law and ordinance.
Required system shall also include systems agreed to by the city fire
department and building owner/ occupant as an alternative to other code
requirements that are difficult or impractical to comply with.
Knox box entry systems shall mean approved key boxes manufactured
by Knock Company that meet the specification and approval of the city fire
department. These key boxes are for the exclusive use of the city
fire department for emergency purposes only.
(Ord. No. 00-7, § I, 5-8-00)
Sec. 30-118. Adoption of fire
alarm systems requirements.
(a) The installation, maintenance, operation and transmission of
fire alarm systems, to which the city fire department may respond
including non-required systems, shall be in accordance with the
requirements of the National Fire Protection Association 72 (National Fire
Code) 1996 Edition or currently adopted edition. In addition fire
alarm systems shall be subject to the amendments set forth in section
30-120 of this article.
(b) This article adopts
by reference the following codes and standards as they apply to automatic
fire alarm systems.
NFPA 72 National Fire Alarm Code 1996
Edition;
NFPA 70 National Electrical Code;
NFPA 13 Installation of Sprinkler
Systems1996 Edition
(c) If there is any conflict between the
language of this article and the language of the aforementioned codes and
standards, the most restrictive shall apply.
(Ord. No. 00-7, § I, 5-8-00)
Sec. 30-119 Applicability
These requirements of this
article shall apply to all new buildings within inspection boundaries of
the city fire department.
(1) New buildings should comply with the requirement of this article
before the building is occupied or used for any purpose other than its
construction.
(2) False alarm provisions shall apply to both new and existing
structures.
(3) All costs associated with the installation, operation,
transmission, and maintenance of automatic fire alarm systems shall be
borne by the building owner/ and or occupant.
(Ord. No. 00-7, § I, 5-8-00)
Sec. 30-120. Amendments.
The codes adopted in section 30-118 of this
article are hereby amended as follows:
(1) Transmission
of alarm signals:
a. All alarm signals emanating from
automatic fire alarm systems shall transmit by dedicated circuit.
b. Non-required systems may transmit clear
signals via digital communicator with a daily test signal or other
means to a UL listed central station. All alarm signals received by
the central station must be relayed to the city fire department alarm
center via public switched telephone network at (414)248-4434 or at
said number as established from time to time. A copy of the current UL
listing for central station alarm receiving locations shall be on file
at the city fire department. Alarm installation company shall provide
for current UL listing for central stations. Note: After September 25,
1999, the area code will change to (262).
c. Systems that transmit alarm via recorder
or digital voices shall be prohibited. No fire alarm system shall be
programmed to directly dial 911 or other emergency and/or
non-emergency number of the city fire department.
(2) Registration
and permits:
a. All new automatic fire alarm systems,
and modification to existing systems, shall be reviewed by the city
fire department prior to installation or modification.
1. A minimum of two sets of detailed plans
and specifications shall be submitted to the city fire department
before any automatic fire alarm system is installed or altered.
2. A minimum of one set of approved plans
and specifications shall be on the job at all times.
3. A plan review fee of $50.00 shall be
submitted with the detailed plans. A fee of $25.00 per hour will be
charged for witness testing of the system.
4. All fire alarm systems shall be
inspected by and tested in the presence of the city fire department
fire prevention bureau before it is placed in service. An appointment
for acceptance and testing shall be made five days prior to the final
testing.
5. The authority having jurisdiction shall
be authority to disconnect primary power and seal the panel a minimum
of 24 hours prior to the acceptance test. If seal is broken or opened
the final acceptance test will not be done that day and additional
charges will be incurred.
b. All fire alarm systems shall be
registered with the city fire department fire prevention bureau on a
form provided. A list of at least three key holders including home,
work and pager telephone numbers shall be submitted on supplied forms
prior to acceptance. It shall be the responsibility of the
owner/occupant to update this registration whenever changes occur.
(3) Knox
Box entry system:
a. All new and existing occupancies having
automatic fire alarm systems shall have approved Knox Box systems
installed in a location approved by the city fire department.
b. The Knox Box shall contain all keys for
all locked areas of the building as required by the city fire
department. Keys shall include, but not be limited to, all areas of
the building, automatic fire alarm systems, pull station re-setting
tools, all elevators and elevator machine rooms and sprinkler systems
riser rooms.
c. The city fire department shall be
notified immediately of changes of locks and/or keys for the building
to allow for the placement of new keys in the Knox Box.
(4) Zoning
of fire alarm systems:
Shall be, per NFPA 72, 1-5-7.
(5) Additional
specific system requirements:
a. All fire alarm control panels shall be
capable of silencing the audio notification signal without re-setting
the panel. The silencing switch shall be a single switch requiring no
keys, access codes or special knowledge. The re-set switch shall be a
single switch requiring no keys, access codes or special knowledge.A
key may be used to actuate a remote annunciator panel to silence a
system.
b. All wiring should conform to the most
recent requirements of NFPA 72 (National Fire Alarm Code) and the
National Electrical Code.
c. All smoke detectors should have
indicting lights that illuminate when the detector activates. When
smoke detectors are installed in any location not visible from the
floor area, remote indicating lights shall be provided in a location
approved by the city fire department.
d. The installation of safety guards over
alarm initiating devices may be required when such devices are subject
to damage or frequent malicious activation.
e. All sprinkler system control valves and
associated control functions shall be equipped with electric
supervision including pump power, pump run and room temperature etc.
Supervised functions shall transmit a separate and distinct
supervisory alarm. Said alarm should automatically restore when the
supervised function is restored to the normal position and indicates
restoration at the remote alarm monitoring station.
f. Alarm system indicating panels shall be
placed so that fire fighting personnel do not have to pass through or
into the structure any further than the main entrance to view or
operate the alarm panel.
(6) Vacant
buildings:
The alarm system shall remain in operation at all times.
(7) Maintenance
and repair of systems:
All building owners and/or occupants shall maintain their automatic
fire alarm systems in good operating condition at all times.
a. Every automatic fire alarm system
shall be inspected annually or more frequently if required by NFPA 72,
by a licensed fire alarm
contractor. Systems shall be cleaned when
necessary. Proof of such inspection shall be filed with the city fire
department fire prevention bureau with 15 days of the inspection.
b. If a system malfunctions or otherwise
needs repair, the building owner and/or occupant shall see that said
repairs are performed by a licensed fire alarm contractor or
electrician within 24 hours of discovery.
c. Automatic fire alarm systems that
transmit more than two false alarms in a 24-hour period or more three
false alarms in a seven-day period may be taken out of service by the
city fire department. Automatic fire alarm systems taken out of
service necessitates the establishment of a human fire watch, 24 hours
per day until the system is repaired and the entire system is
functional.
(Ord. No. 00-7, § I, 5-8-00)
(a) False
alarms, administrative charges:
(1) The owner or occupant shall be charged
for fire protection system malfunctions and/or false alarms generating
true fire alarm condition in excess of three per calendar year at the
following rates:
Fourth false alarm . . . $300.00
Fifth and all subsequent false alarms (each)
. . . 500.00
(2) The owner or occupant shall be charged
for fire protection system trouble or supervisory alarms in excess of
five per calendar year, that results from any reason other than system
testing, maintenance, electrical service, telephone line, or weather
malfunction at the rate of $300.00 per alarm.
(3) No person shall deliberately or
maliciously turn in an alarm of fire when in fact that person knows
that no fire exists. No person shall activate any automatic fire alarm
system or installed fire protection system for purpose other than
emergency, maintenance, drills or prescribed testing. A fine of
$500.00 shall be charged for false alarms and/or up to 30 days
imprisonment.
(4) This subsection is intended to impose a
strict liability on the person, business, corporation or other entity
responsible for alarm connections to alarm receiving firm to which the
fire department has responded and shall be applied regardless of the
cause of the false alarm except those situations as defined in section
30-121(a)(2). Failure to pay such administrative charge(s) in and of
itself shall constitute a violation of this section.
(1) No person other than a fire official,
shall cause a fire alarm system to be reset once an alarm has been
activated. This section will not apply to alarms generated for testing
or fire drills when the fire department has been notified of the
testing or drill.
(2) Alarm system audio warning devices may
be silenced by the building owner/occupant, but only after a thorough
search of the building has been conducted and it is determined that no
fire or other emergency exists.
(Ord. No. 00-7, § I, 5-8-00)
|