|
Article II. Automatic Sprinkler Systems
Cross references: Businesses, ch 18
State Law References: Duties of fire chief regarding fire prevention
generally, W.S.A. § 101.14(2); enforcement of business codes generally,
W.S.A., §, 62.17.
Sec. 30-31 Purpose and intent of article.
The intent of this article is designed to require the installation of
automatic fire suppression systems for the better protection of life and
property within the city.
(Ord. No. 95-9, § I, 7-10-95)
Sec. 30-32. Buildings requiring installation.
(a) This article requires the installation of an automatic fire
sprinkler system in the following buildings:
(1) Multifamily;
(2) Industrial;
(3) Government Buildings;
(4) Hotels;
(5) Dormitories;
(6) Nursing;
(7) Old age and other institutional buildings;
(8) Commercial;
(9) Intuitional;
(10) Public Buildings;
(11) Motels;
(12) Rooming houses and;
(13) Convalescent
(b) A complete approved automatic fire sprinkler protection system
shall be provided in all the buildings listed in subsection (a) of this
section, except multifamily, as follows:
(1) Fire-resistive buildings.
Throughout every building which is either:
(a) Ten
thousand feet or more in total area;
(b) Is over
one story in height and exceeds 6000 square feet in total area; or
(c) Is over
two stories in height.
(2) Non-fire resistive buildings.
Throughout every building which is either:
(a) Five
thousand square feet or more in total area; or
(b) Is over
two stories in height.
(Ord. No. 95-9, § I, 7-10-95)
Sec. 30-33. Accessory buildings and special
principal building areas.
Approved automatic sprinkler equipment shall be installed and maintained
in the following accessory buildings and special principal building areas
as follows:
(1) Garages. Automatic sprinkler equipment shall be
installed in garages as follows:
a. Garages within, attached to above or below other
occupancies.
b. Garages used as passenger terminals.
(2) Basements and subbasements. In the basements and
subbasements of principal and accessory buildings approved automatic
sprinkler equipment shall be installed as follows:
a. All basements having a total floor area of 2,500
square feet or more.
b. All subbasements regardless of size.
(3) Multifamily buildings. All multifamily buildings
which exceed the thresholds established in chapter ILHR 66 Uniform
Multifamily dwellings, Table 66.33-B, shall have automatic fire sprinklers
installed unless the building is provided with two-hour fire separations
as required by chapter ILHR 66.
(4) Daycare centers, including adult day care
centers. All buildings in day care centers and adult day care centers,
regardless of size, shall have complete sprinkler protection throughout.
(5) Community based residential facilities (CBRF).
All buildings in community based residential facilities (CBRF), regardless
of size, shall have sprinkler protection throughout.
(6) Theaters and assembly buildings. All buildings
in theaters and assembly buildings, regardless of size, shall have
sprinkler protection throughout.
(7) Hospitals, nursing, convalescent, old age and
other similar institutional buildings. All buildings of nonfire-resistive
construction in hospitals, nursing, convalescent, old age and other
similar institutional buildings, regardless of size, shall have sprinkler
protection throughout.
(8) Schools, colleges and universities. All
buildings of nonfire-resistive construction in schools, colleges and
universities, regardless of size, shall have sprinkler protection
throughout.
(9) Dormitories, fraternities and sorority houses.
All buildings in dormitories, fraternities and sorority houses, regardless
of size, shall have sprinkler protection throughout.
(10) Hotels, motels and roominghouses. All buildings
of nonfire-resistive construction in hotels, motels and roominghouses,
regardless of size, shall have sprinkler protection throughout.
(11) Commercial, industrial and institutional
garages and service centers. Any building with a total area of 3,000
square feet in area or greater in commercial, industrial and institutional
garages and service centers, regardless of size, shall have sprinkler
protection throughout.
[Ord. No. 95-9, $ I, 7-10-1995]
-
Sec. 30-34. High-hazard occupancies.
(a) Approved automatic fire suppression equipment
shall be installed and maintained in the following buildings, regardless
of size, in which it is expected there will be high-hazard occupancy,
including, but not limited to:
(1) Aircraft hangars.
(2) Dry cleaning establishments using or storing
gasoline or other volatile flammable liquids.
(3) Enameling or Japanning operations.
(4) Mills: Sugar, starch, cereal, feed, hay flour
and grist mills.
(5) Paint and varnish: Manufacturing, storing,
handling, spraying and other related operations.
(6) Paint stripping establishments.
(7) Manufacture and storage of Pyroxylin products.
(8) Smoke houses.
(9) Storage of explosive gages under pressure (15
psi and over 5,400 cubic feet) such as acetylene, hydrogen and natural
gas.
(10) Storage of materials with a flashpoint under
200° F., such as celluloid products, kerosene, etc.
(11) Woodworking and other such establishments
with combustible dust.
(12) Chemical works and/or storage facilities.
(13) Explosive and pyrotechnics manufacturing.
(14) Oil refineries.
(b) This article applies to all new
construction after the effective date of the ordinance from which this
section is derived
[Ord. No. 95-9, § I, 7-10-1995]
-
Sec. 30-35. Approval of plans.
[Ord. No. 95-9, § I, 7-10-1995]
(a) Submission for review by fire chief. Prior
to the installation of any portion of a fire suppression system, or
the alteration to an existing fire suppression system, plans shall be
submitted to the fire chief for review. All fire suppression systems
must comply with all applicable NFPA standards.
(b) Stamping, signing and sealing of plans. Four
copies of the plans, specifications and calculations shall be
submitted for review; reviewed plans shall be stamped "conditionally
approved by the fire prevention bureau." Two copies will be returned
to the submitter. One copy with the "conditionally approved by the
fire prevention bureau" stamp must remain on the job site at all
times. All copies of the plans, specifications and calculations
submitted shall be signed and sealed by a state registered architect,
fire protection engineer, fire protection designer or the qualifier
before the fire suppression contractor installs the work. Plans and/or
calculations which are not signed and sealed will not be reviewed.
(c) Conditional approval; effect. The city fire
department's conditional approval of fire suppression plans does not
affirm the accuracy of any calculations performed by the contractor.
Full responsibility for the accuracy of the system design and
calculations is the responsibility of the fire protection contractor.
(d) Work not to commence prior to plan review
and permit issuance. No work may begin on the installation of any fire
suppression system or the alteration of an existing system until the
plans, specifications and calculations have been reviewed by the city
fire department and a permit for installation is obtained.
-
Sec. 30-36. Installation methods and
standards.
[Ord. No. 95-9, § I, 7-10-1995]
(a) Approved fire suppression systems shall be
installed in accordance with current National Fire Protection
Association (NFPA) standards and/or recommended practices which are
applicable.
(b) All fire sprinkler systems shall use hydrant
water flow test data which is dated no greater than six months prior
to the submission of the sprinkler plans for review. The data shall be
obtained during peak water demand conditions, and conducted in such a
manner that it represents true orientation (direction of flow) of the
supply to the system being designed.
(c) All sprinkler system designs shall be based
on no more than 90% of the available water supply. A minimum safety
factor of 10% shall be maintained.
(d) All fire suppression systems shall be
installed in accordance with all applicable state codes.
(e) Fire department connections. The location of
all fire department connections shall be approved by the fire chief.
(f) Audible alarm bells are required on the
inside and outside of all buildings.
-
Sec. 30-37. Maintenance of equipment.
[Ord. No. 95-9, § I, 7-10-1995]
(a) All fire suppression equipment shall be
maintained in proper working order in accordance with the state code.
(b) The fire department shall be notified prior to
shutting down any system for any reason and again when the system has
been restored to service
-
Sec. 30-38. Inspections.
[Ord. No. 95-9, § I, 7-10-1995]
(a) All fire sprinkler systems shall be
inspected, tested and maintained in accordance with NFPA 25, 1991
edition. A copy of all inspection and testing reports shall be sent to
the fire department on a yearly basis and/or if requested by the fire
chief or fire inspector.
(b) Inspections of fire suppression systems
during construction will be made by the fire department or their
designated representative.
(c) The fire protection contractor must request
an inspection prior to any fire protection system component being
concealed.
(d) The fire protection contractor must request
an inspection upon completion of the system installation.
(e) The fire protection contractor must request
an inspection 24 hours in advance.
-
Sec. 30-39. Testing of systems.
[Ord. No. 95-9, § I, 7-10-1995]
The following tests shall be witnessed by
the fire department or its representative:
(1) Fire protection water supply hydrostatic
test.
(2) Fire protection water supply flushing.
(3) Sprinkler system hydrostatic test.
(4) Standpipe system hydrostatic test.
(5) Dry sprinkler system air/hydrostatic
test.
(6) Dry pipe valve trip test.
(7) Deluge system trip test.
(8) Fire pump acceptance test.
(9) Carbon dioxide system acceptance tests.
(10) Dry chemical system acceptance tests.
(11) Foam system acceptance tests.
(12) Special agent system acceptance tests.
(13) Standpipe system acceptance tests.
(14) Full flow backflow preventer tests.
(15) Sprinkler system acceptance tests.
(16) Foam system acceptance tests.
(17) Fire hydrant flow tests.
(18) The fire protection contractor must
request the fire department to witness all testing at least 24 hours
in advance.
-
Sec. 30-40. Fees.
[Ord. No. 95-9, § I, 7-10-1995; Ord. No.
06-04, § I, 2-27-2006]
Fees for the following items shall be
charged;
(1) Basic fire sprinkler plan review.
(2) Each additional review of the same
system.
(3) Fire pumps per review.
(4) Modifications to existing sprinkler
systems.
(5) Review of additional hydraulic
calculations only.
(6) Fire protection underground piping.
(7) Fire hydrants.
(8) Fire hose connections.
(9) Standpipe systems.
(10) All other suppression systems.
(11) Inspections.
(12) Witness tests.
|